YT-1000 Series E/P Positioner

The Electro-Pneumatic Positioner YT-1000 is used for operation of pneumatic rotary or linear valve actuator by means of electrical controller of control systems with an analog output signal of DC 4 to 20mA or split ranges.

 

• There is no resonance at 5-200Hz.

• The change of RA/DA acting is convenient.it is able to apply to apply to single or double acting actuator.

• It is possible to prevent the hunting with orifice to the small size actuator.

• It is economical due to less air consumption.

• It is able to control the 1/2 split range with simple operation with replacement of parts.

Parameters

TypeItem Single Acting Double Acting
Input Signal 4-20mADC
Imped dance 250±150hm
Supply Pressure 1.4~7Kg.f/cm?(20~100psi)
Stroke 0-90°
Air Conn 1/4*PT(NPT)
Gauge Conn 1/8″PT(NPT)
Electric Conn 1/2PT(NPT, PF)
Explosion proof And dI IBT 6 And dI ICT 6 And iaI ICT 6
Prot rc tion IP66
With.Temp -20~60℃(-4~158°F)
Linearity ±1%F.S. ±2%F.S
Hysteresis ±1%F.S.
Sensitivity ±0.2%F.S. ±0.5%F.S.
Repeat abl ty ±0.5%F.S.
AirCon sun mpi is 3LPM(Sup=1.4kg.f/cm?, 20psi
Flow Capacity 80LPM(Sup=1.4kg.f/cm?, 20psi
Material Aluminum, Die-Casing
Weight 2.8kg(6.2Ib)
Note: Pleasespecifythethreadtypeofair&electricconnectionuponorder.
YT-1000R is used for operation of pneumatic rotary valve actuator by means of electrical controller of control systems with an analog output signal of DC 4 to 20mA or split ranges.
3-3fgh
YT-1000L is used for operation of pneumatic linear valve actuator by means of electrical controller of control systems with an analog output signal of DC 4 to 20mA or split ranges.
3-44bi

Confirm the Right YT-1000 Series E/P Positioner

Send the valve type, size and torque, the air supply or voltage, and whether it should fail open, fail close or stay in place. The quotation is confirmed against that duty.

Request a Quote